boiler from the mains, now unscrew the heater and clean up the area in which it is
located.
Possible
cause 4
CAUSE 4
– Deep area of the combustion space where the pellets are burning is full of
unburnt residues, i.e. of the slag so that there is no contact of pellets and hot air.
The procedure for
troubleshooting 4
– Clean the deep area of the combustion chamber,
first clean the rough particles of slag mechanically and the fine slag can be removed by
means of vacuum cleaner.
Possible
cause 5
CAUSE 5
– Pellets used are of high humidity.
The procedure for
troubleshooting 5
– Try to use pellet that has a higher level of
dryness.
Possible
cause 6
CAUSE 6
– Electric supply voltage onto which the boiler is connected is much lower
than 220-230V so the capacity of the heater is lower.
The procedure for
troubleshooting 6
– Connect the AC Voltage adapter or ignite
manually.
Possible
cause 7
CAUSE 7
– After the manual setting and automatic addition in the ignition area the pellet
level is such that the pellet is not in contact with the heater.
The procedure for
troubleshooting 7
– Re-charge the level of pellets.
Possible
cause 8
CAUSE 8
– The boiler is set from automatic to manual mode of operation. If, along the
whole phase of ignition, the heater lamp is not lighted, then we are sure that the boiler is
in manual mode.
The procedure for
troubleshooting 8
– Switch the boiler into automatic ignition.
Possible
cause 9
CAUSE 9
– Faulty electric heater for ignition.Switch off the boiler from the mains
supply and on the the electrical heater cords measure the resistance.
The procedure for
troubleshooting 9
– Change electric heater.