The hydraulic separator creates an area with
reduced load loss, which allows hydraulically
rendering independent the primary and secondary
circuits connected to it. With the hydraulic separator
you can thus have a production circuit with constant
heat capacity and a distribution circuit with variable
heat capacity, operation conditions typically specific
to modern air-conditioning systems.
Particular attention should be given, during the
design phase, to possible temperature variations
to which the circuits can be subject due to the
generated mixing inside the hydraulic separator.
A secondary circuit with a heat capacity higher
than the circulatory one of the primary circuit
generates, in fact, by means of the hydraulic
separator, a delivery temperature lower than the
one of the primary circuit.
INSTANTANEOUS D.H.W. PRODUCTION KIT - R1K
75-R1K 100 - ON UNIVERSAL FRAME
The kit, in combination with a plate exchanger, allows
instantaneous D.H.W. production. It is installed on
the universal frame. The kit (Code 65-00837, fig.2),
in addition to the pipes and the and a fixing bracket,
includes a plate exchanger (50 plates), a flow meter
to be installed onto the inlet cold water pipe and a
D.H.W. clip sensor to be fitted onto the DHW outlet
pipe.
cod. 65-00837
fig. 2