2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P26
MODBUS ADDRESS
BY MEANS OF THIS PARAMETER, IT IS POSSIBLE TO
SET THE ADDRESS OF THE BOARD ON MODBUS IN
ORDER TO PERFORM A CASCADE SYSTEM.
1 - 16
BOILER
NUMBERING
FOR
MODBUS
P27
ACTIVATION PERCENTAGE OF THE SECONDARY UNIT
60 - 100
THE VALUE IS EXPRESSED IN
PERCENTAGE
(PRE-SET BY DEFAULT TO 85%)
P28
DEACTIVATION PERCENTAGE OF THE SECONDARY
UNIT
5 - 40
THE VALUE IS EXPRESSED IN
PERCENTAGE
(PRE-SET BY DEFAULT TO 10 %)
P29
ENABLING THE MASTER BOARD WITH CRAD AREA
MANAGEMENT BOARD
0 - 2
0 = DISABLED (PRE-SET BY
DEFAULT)
1 = CRAD AREA BOARD
CONNECTED
2 = CRAD AREA BOARD
CON REMOTE
P30
SETTING THE TEMPERATURE MEASUREMENT UNIT
THROUGH THIS PARAMETER, YOU CAN SELECT
THE MEASUREMENT UNIT OF THE DISPLAYED
TEMPERATURE:
CELSIUS (°C) OR FAHRENHEIT (°F) DEGREES.
0 - 1
0 = °C
1 = °F
P31
SELECTION OF THE COUNTRY OF DESTINATION
BY CHANGING THIS PARAMETER, THE CONTROL
PARAMETERS OF THE COMBUSTION ARE
AUTOMATICALLY CONFIGURED ACCORDING
TO THE VALUES PRE-SET IN THE COUNTRY OF
DESTINATION OF THE PRODUCT.
0 - 1
0 = OTHER COUNTRY
1 = U.S.A. / CANADA
P32
DOMESTIC CIRCUIT OPERATING MODE
0
-
2
0 = DOMESTIC CIRCUIT BY
MEANS OF BOILER PROBE
1 = DOMESTIC CIRCUIT BY
MEANS OF THERMOSTAT
2 = DOMESTIC CIRCUIT BY
MEANS OF MODBUS