2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P18
ENABLING BUS INDUSTRIAL PILOTING 0 -10V
THROUGH THIS PARAMETER YOU CAN ENABLE
OR DISABLE THE BUS INDUSTRIAL INPUT 0-10 V
TO SET THROUGH EXTERNAL BUS THE BURNER
POWER OR THE DELIVERY TEMPERATURE.
0 - 2
0 = DISABLED
(SET BY DEFAULT)
1 = TEMPERATURE CONTROL
MODE
2 = POWER CONTROL MODE
P19
MINIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET
THE USER-ADJUSTABLE MINIMUM HEATING
TEMPERATURE.
20 - 40
THE VALUE IS EXPRESSED IN °C
P20
MAXIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET
THE USER-ADJUSTABLE MAXIMUM HEATING
TEMPERATURE.
40 - 90
THE VALUE IS EXPRESSED IN °C
P21
MAXIMUM DOMESTIC SETPOINT
(only for RS version with remote storage system)
THROUGH THIS PARAMETER YOU CAN SET
THE USER-ADJUSTABLE MAXIMUM DOMESTIC
TEMPERATURE.
45 - 75
THE VALUE IS EXPRESSED IN °C
P22
SET POINT
'
T DELIVERY-RETURN
THROUGH THIS PARAMETER YOU CAN SET THE
TEMPERATURE DIFFERENCE BETWEEN DELIVERY
AND RETURN.
0
0 = DISABLED
10 - 40
THE VALUE IS EXPRESSED IN °C
P23
MODULATING PUMP MINIMUM SPEED
THROUGH THIS PARAMETER YOU CAN SET THE
MINIMUM SPEED VALUE OF THE MODULATING
PUMP DURING A REQUEST TO OPERATE IN
HEATING MODE.
50 - 70
THE VALUE IS EXPRESSED IN
PERCENTAGE
P24
MODULATING PUMP MAXIMUM SPEED
THROUGH THIS PARAMETER YOU CAN SET THE
MAXIMUM SPEED VALUE OF THE MODULATING
PUMP DURING A REQUEST TO OPERATE IN
HEATING MODE.
70 - 100
THE VALUE IS EXPRESSED IN
PERCENTAGE
P25
CONTROL PERIOD
'
T DELIVERY-RETURN
THROUGH THIS PARAMETER YOU CAN SET THE
RESPONSE TIME TO THE PUMP MODULATION.
20 - 100
THE VALUE IS EXPRESSED IN
SECONDS