2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P70
ENABLING OF SECURITY CONTROL FOR INSUFFICIENT
CIRCULATION AT EVERY IGNITION
THROUGH THIS PARAMETER IT IS POSSIBLE TO
CHECK THE CORRECT OPERATION OF THE PUMP
AT EVERY IGNITION OF THE BURNER. THIS CHECK
ALLOWS PROTECTING THE HEAT EXCHANGER AND
OTHER PARTS FROM EXCESSIVE NON-DISSIPATED
HEAT, IN CASE THE PUMP IS NOT PROPERLY
OPERATING.
0 - 1
0 = DISABLED
1 = ENABLED (SET BY DEFAULT)
P71
ACTIVATION AND OPERATING MODE OF THE CONTACT
‘CT’ THROUGH ACCESSORY COD. 40-00133 (SEE
CHAPTER “OPTIONAL ELECTRICAL CONNECTIONS”)
THIS PARAMETER IS AUTOMATICALLY SET TO THE
VALUE ‘1’ WHEN THE VALUE OF PARAMETER P00 IS
SET TO ‘4’.
0 - 2
0 = DISABLED (SET BY DEFAULT)
1 = AIR PRESSURE-SWITCH
SAFETY
2 = TELEPHONE DIALER
P72
ACTIVATION OF THE CONTACT “CSF - WATER FLOW
SWITCH” (SEE CHAPTER “MASTER BOARD ELECTRICAL
CONNECTIONS”)
THE ACTIVATION OF THIS PARAMETER ENABLES
TO MONITOR THE ACTUAL WATER CIRCULATION,
THRU AN EXTERNAL WATER FLOW SWITCH.
0 - 1
0 = DISABLED (SET BY DEFAULT)
1 = ENABLED