60
R1K 120 - RAD - ING - Manuale - 2201.1_SKM1_no_INAIL_firm.L226F
2 D
a
ti te
cnici
_
R
1
K 1
2
0
_
SK
M
1
_
E
N
2. MAINTENANCE
SER
VICE
CENTRE
2.2.8. TECHNICAL DATA
Model
R1K 120
CE certification
no.
-
Gas category
(IT) II2H3B/P
Discharge type
type
B 2 3 - B 2 3 p - B 3 3 -
C13-C33-C43-C53-
C63-C73-C83-C93
Energy efficiency 92/42 CEE
no. stars
4
Maximum nominal heat capacity in heating circuit
kW
118
Minimum nominal heat capacity in heating circuit
kW
6
Useful thermal power - 60/80°C
kW
114.46
Performance at 100% Pn - 60/80°C
%
97
Average efficiency Pn - 60/80 ° C
%
97.8
Performance at 30% Pm - return 30°C
%
108.3
Maximum combustion Performance
%
97.2
Minimum combustion Performance
%
98.2
Fumes temperature at nominal heat capacity
°C
81.2
Fumes temperature at minimum heat capacity
°C
58.7
CO2 at nominal heat capacity - G20
%
9,4 - 9,2
CO2 at minimum heat capacity - G20
%
9,1 - 8,9
CO2 at nominal heat capacity - G30
%
11,4 - 11,2
CO2 at minimum heat capacity - G30
%
10,8 - 10,6
CO2 at nominal heat capacity - G31
%
10,3 - 10,1
CO2 at minimum heat capacity - G31
%
9,8- 9,6
CO at nominal heat capacity
ppm
87
CO at minimum heat capacity
ppm
1
Weighted CO (0% O2)
ppm
8
Casing efficiency losses (full load)
%
0.20
NOx class
class
6
Weighted Nox (0% O2) mg/kWh
mg/kWh
38
Heating circuit
Adjustable heating temperature
°C
30-80 / 25-45
Maximum operating temperature for heating circuit
°C
80
Maximum operating pressure for heating circuit
bar
3
Minimum operating pressure for heating circuit
bar
0.3
Dimensional characteristics
Width
mm
670
Depth
mm
485
Height
mm
640
Gross weight
Kg
74
Water connections
Flow
Ø
1 1/2”
Gas
Ø
1”
Return
Ø
1 1/2”
Fume exhaust fittings
Maximum electric fan pressure available
Pa
100 (Single unit)