Exceptions:
For any channels programmed for “Status Only” or for Run Time Meter function, use
code 1 ZZ for the Open Circuit message, and 2 ZZ for the Closed Circuit message.
If you run out of recording time, you will hear the message “No more message time."
You may elect to shorten some messages, or rely more on selected default messages,
or you may Autoextend the available recording time. Then, re-record all messages.
If you wish to extend the available time for a specific message while leaving the other
messages unaffected, enter the code for recording that message, but add an extra digit
1 through 4, before pressing ENTER. The digit 1 (Rate 1) gives the shortest time and
the best sound quality, while 4 (Rate 4) gives the longest time with the poorest sound
quality.
If you wish to reinstate a default message, enter the code for recording that message,
and an extra POINT before pressing ENTER. For example:
1 ZZ POINT ENTER
If you wish to use the default Station ID message but with a different ID number in place
of the “one”, press:
9 1 4 N ENTER
where N is the desired ID number which may be up to 16 digits long. Some users
program the Verbatim autodialer’s own phone number as its ID number.
If you want to set a specific recording rate rather than letting Autoextend do it, press:
9 1 3 N ENTER
where N is the desired recording rate 1, 2, 3 or 4. You will then need to re-record any
messages that were previously recorded at a different rate.