All contact inputs are initially set normally closed (i.e. they will alarm on Open Circuit).
This is the default setting and, therefore, any open circuits, including any inputs left
disconnected during installation, will appear as alarms until the inputs are programmed.
To automatically program the inputs: Make sure all inputs are in their normal
(non-alarm) state. Then press:
5 0 0 ENTER
The Verbatim autodialer automatically examines all inputs and programs them to alarm
on the opposite input state from their present status. This code 500 does not affect any
channels that have been programmed for Disabled Channels, Status Only, Run Time
Meter, or Pulse Totalizer function.
Exceptions:
In most cases, no further programming of contact inputs is necessary. However, the
following configuration options are available:
To set any input to be
disabled
and never be annunciated, press:
5 ZZ 0 ENTER
where ZZ is the 2 digit channel number you are programming. Be sure to always use a
leading 0 for channels 1 through 9 to keep the channel number a two-digit entry.
To set an individual contact input for
normally closed
operation (i.e. to alarm on Open
Circuit), press:
5 ZZ 1 ENTER
To set an individual contact input channel for
normally open
operation (i.e. to alarm on
Closed Circuit), press:
5 ZZ 2 ENTER
To set inputs to report
status only
, program each channel as follows:
5 ZZ 3 ENTER
This setup never causes an alarm to dial out.