Quasar CM-6208 User and Installation Guide
52
9.3.4
Events Setup
The
Events Setup
tab includes the following functions:
IO
Network Failure Detection
Tampering
Periodical Event
Manual Trigger
IO
The
IO
screen enables control over the input and output alarms. If, for example, an event is
recognized by the system, an input or output alarm and message is generated.
Figure 55: IO Screen
Alarm Switch
The Administrator can select from the following options:
Select
Off
to disable an alarm.
Select
On
to enable an alarm (default setting).
Select
By
Schedule
to set a schedule. Then click
Please Select
to select up to 10 schedules
from the drop-down list that opens. The selected schedules are displayed in the
Please
Select
text box. To set a schedule, open the
Schedule
tab.
Click
Save
after configuring the settings.
Alarm Type
Select an alarm type (
Normal close
or
Normal open
) that corresponds to the alarm application.
Normal open
is the default setting. Click
Save
after configuring the settings.
Alarm Output
Define the normal alarm output signal as
Output high
or
Output low
, according to the current alarm
application.
Output high
is the default setting. Click
Save
after configuring the settings.