ACL 4/52 Software Interface Guide
Document 6211225-03
Version 3.0
Events
2-7
Power Cycle
When the library is powered on it generates a “Power On/Reset
Occurred” event (SK=6 ASC=29 ASCQ=00).
Library Unit Off-line/Standby
When a library is placed into the off-line/standby state, it generates a
“Logical Unit Standby Button Was Pressed” event (SK=6 ASC=80
ASCQ=09).
Library Unit On-line Initialization Failure
When a library is placed into the on-line state and the on-line
initialization fails, the library generates an event for the specific error
condition that caused the failure. The control panel indicates which
state of the initialization failed (see Appendix B for more information).
Library Unit Door Opened
When the front door of a library is opened, the library disables all
actuators and generates a “Door Was Opened” event (SK=6 ASC=80
ASCQ=00).
Library Unit Stopped
When the library is stopped by pressing the STOP switch on the
control panel, the library disables all actuators and generates a
“System Stop Button Was Pressed” event (SK=6 ASC=80 ASCQ=07).
Accessed Load Port
When the Load Port door is closed, the library generates an “Import or
Export Element Accessed” event (SK=6 ASC=28 ASCQ=01).
Maximum Temperature Exceeded
The library monitors the ambient temperature within the system. If the
temperature exceeds 91.4
ο
F, there is a possibility for potential damage
to the medium, the library generates a “Warning Safe Temperature
Exceeded” event (SK=6 ASC=88 ASCQ=00) and continues operations.
If the temperature exceeds 96.8
ο
F, the library disables all actuators
until the temperature decreases and generates a “Maximum
Temperature Exceeded” event (SK=4 ASC=88 ASCQ=01).