QUANTECH
76
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
SECTION 4 - TECHNICAL DATA
TABLE 26 -
WATER FLOW RATE LIMITS GPM (L/S) (BASED UPON STANDARD TUBES AT DESIGN
FULL LOAD CONDITIONS)
PIN 5, 6
EVAPORATOR
PIN 7, 8
CONDENSER
2 PASS
3 PASS
1 PASS
2 PASS
3 PASS
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
BB
240
(15)
750
(47)
160
(10)
490
(31)
BB
390
(25)
1560
(98)
190
(12)
780
(49)
130
(8)
520
(33)
BC
280
(18)
870
(55)
190
(12)
570
(36)
BC
440
(28)
1780
(112)
220
(14)
890
(56)
150
(9)
590
(37)
BD
330
(21)
910
(57)
220
(14)
660
(42)
BD
480
(30)
1950
(123)
240
(15)
910
(57)
—
—
CB
240
(15)
750
(47)
160
(10)
490
(31)
CB
390
(25)
1560
(98)
190
(12)
780
(49)
130
(8)
520
(33)
CC
280
(18)
870
(55)
190
(12)
570
(36)
CC
440
(28)
1780
(112)
220
(14)
890
(56)
150
(9)
590
(37)
CD
330
(21)
910
(57)
220
(14)
660
(42)
CD
480
(30)
1950
(123)
240
(15)
910
(57)
—
—
DB
240
(15)
750
(47)
160
(10)
490
(31)
DB
390
(25)
1560
(98)
190
(12)
780
(49)
130
(8)
520
(33)
DC
280
(18)
870
(55)
190
(12)
570
(36)
DC
440
(28)
1780
(112)
220
(14)
890
(56)
150
(9)
590
(37)
DD
330
(21)
910
(57)
220
(14)
660
(42)
DD
480
(30)
1950
(123)
240
(15)
910
(57)
—
—
The expected waterside pressure drop at design flow is provided on the particular chiller sales order form header.
When rated in accordance with AHRI-550 standard, the actual pressure drop for clean tubes is permitted to be
lower than of 15% greater than the stated value.
To determine flow or waterside pressure drop at conditions other than sales order design, use the following rela-
tionship and solve for the unknown parameter. Be sure to use consistent units of measure:
Design Flow
Design Pressure Drop
Actual Flow
Actual Pressure Drop
=
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...