QUANTECH
145
SECTION 7 - MAINTENANCE
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
7
The pipe plug has straight threads, and
could fall into the reservoir.
5.
Remove the cap on the fill tube and run the cool
-
ant pump to verify the level in the fill tube.
6. Make sure the coolant level in the VSD cooling
system is 1/2 in. (2 cm) from the top of the fill
tube while running.
7. Run the pump by placing the chiller in SERVICE
8. Add new coolant, if necessary.
9. Reinstall the cap before stopping the coolant
pump to avoid overflowing the fill tube when the
coolant
pump is turned off. The coolant system
holds about 2 gal (7.6 L) of coolant.
Preventive Maintenance
It is the owner's responsibility to fulfill the necessary
daily, monthly and yearly system maintenance require-
ments to keep the unit operating at its peak efficiency.
Follow the maintenance schedule in
If a unit fails due to improper maintenance
during the warranty period, Quantech will
NOT be liable for costs incurred to return
the system to satisfactory operation.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...