QUANTECH
106
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
SECTION 6 - OPERATION
Display, if control is enabled.
VI STEP SOLENOID 1 = ON OR OFF
VI STEP SOLENOID 2 = ON OR OFF
RUN TIME
## DAYS ## HOURS ## MINUTES ## SECONDS
RUN SIGNALS RELAY = ON OR OFF
RUN PERM = ON OR OFF SOFTWARE = ON OR OFF
EDUCTOR TEMP
= ###.# °F
TABLE 35 -
SENSOR MINIMUM/MAXIMUM OUTPUTS
SENSOR/INPUT
TYPE
MINIMUM VALUE
MAXIMUM VALUE
*Condenser Pressure
Transducer
0 psig/0 kPa
400.0 psig (2.76 MPa)
Discharge Pressure
Transducer
0 psig/0 kPa
400.0 psig (2.76 MPa)
Oil Pressure
Transducer
0 psig/0 kPa
400.0 psig (2.76 MPa)
Economizer Pressure
Transducer
0 psig/0 kPa
275 psig (1.89 MPa)
Evaporator Pressure
Transducer
0 psig/0 kPa
125.0 psig (.086 MPa)
Cond Liquid Refrig Level
Capacitance
0%
100%
Economizer Temp
3 K Ω Thermistor
18.83°F (-7.31°C)
175.61°F (79.7°C)
Leaving Condenser Liquid
Temp
3 K Ω Thermistor
18.83°F (-7.31°C)
175.61°F (79.7°C)
Entering Condenser Liquid
Temp
3 K Ω Thermistor
18.83°F (-7.31°C)
175.61°F (79.7°C)
Leaving Chilled Liquid Temp
3 K Ω Thermistor
-19.1°F (-28.49°C)
110.2°F (43.4°C)
Entering Chilled Liquid Temp
3 K Ω Thermistor
-19.1°F (-28.49°C)
110.2 °F (43.4°C)
Compressor Motor Temp
10 K Ω Thermistor
-30.2°F (-34.56°C)
302.0° F (150°C)
Discharge Temp
50 K Ω Thermistor
40.3°F (4.61°C)
302.0° F (150°C)
*Evaporator Temp
3 K Ω Thermistor
-4.87°F (-20.3°C)
158.34°F (70.2°C)
*Subcooled Liquid Refrig Temp
3 K Ω Thermistor
18.83°F (-7.31°C)
175.61°F (79.7°C)
Remote Temp Reset
4–20 mA / 2–10 V
0–20 mA / 0–10 V
0%
100%
Remote Current Limit
4–20 mA / 2–10 V
0–20 mA / 0–10V
0%
100%
Condenser Hot Water
Leaving Temp
3 K Ω Thermistor
18.83°F (-7.31°C)
175.61°F (79.7°C)
Condenser Hot Water
Entering Temp
3 K Ω Thermistor
18.83°F (-7.31°C)
175.61°F (79.7°C)
Remote Heat Recovery Temp
Reset Option
4–20 mA / 2–10 V
0–20 mA / 0–10 V
0%
100%
Eductor Temp
3 K Ω Thermistor
18.83°F (-7.31°C)
175.61°F (79.7°C)
* Based on engineering assessment, the "Condenser Transducer", "Evaporator Thermistor" and "Subcooled Liquid Refrigerant Thermistor" are
redundant and can be removed. if these 3 sensors are not physically available, they should be disabled in "SETUP MODE", generally these
setups have been done in plant before shipment, however service people shall re-set them per the description of section "PROGRAM KEY"
under some circumstance such as a controller replaced or software updated.
Sensor Displays
lists all the sensors attached
to the control board associated with SYSTEM DATA
keys. The minimum and maximum values displayed
are provided. If these values exceed the limits, a < (less
than) or > (greater than) sign will be displayed.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...