1. Check the container, valve, discharge line, diffusers and detection
line for any physical damage, deterioration, deformation or corrosion.
If any signs of deterioration, deformation or corrosion are detected,
the defective parts shall be replaced.
2. Check the following on the extinguishing container:
a. The charge status of the extinguishing agent. The gauge pressure
of the valve should be in the green zone (approx. 16 bar at an
ambient temperature of 21°C).
b. The proper fastening of the extinguishing
canister holder.
c. That the temperature of the container does
not exceed the Working Temperature
range (5-50ºC).
Annually or as required by local fire protection regulations,
maintenance must be carried out by an approved company, but
must not be carried out by the users of the equipment because of
the risks involved.