Quadra-Fire • QFP44 • 4051-300 • Rev. U • 4/11
44
11
11
Shrouds
• Chase top shrouds may be fi eld constructed where permitted by regional building codes.
WARNING! Risk of Fire!
Shrouds must be constructed
as specifi ed. Improper construction may overheat chase
top.
NOTICE:
Some regional codes require an agency-Listed
shroud. Consult your local building offi cials.
• The
following
fi eld constructed shroud designs have been tested for Hearth Technologies fi replace systems and termination
caps.
• The shrouds must be constructed from a minimum .018 in. (26 ga) thick aluminized steel.
• The wire mesh is optional but recommended and must be .018 in. thick minimum, 1/2 in. mesh.
A. HHT Shrouds
• You may install a shroud with this fi replace. See Section 17.D. for a list of UL Listed shrouds. Follow the instructions
included with these optional components
Min.
Base Dim.
Min.
Base Dim.
Min.
Top Dim.
Min.
Top Dim.
Figure 11.1 Open Top Shroud Dimensions
B. Field Constructed Shrouds
Open Top Shroud (may be used with DVP-TV, DVP-TVHW, SLP-TVHW)
Min. Base Dims.
in
19 x 19
mm
483 x 483
Min. Top Dims.
in
16 x 16
mm
406 x 406