CASTILE INSERT
D. Full Reline With Outside Air - Vertical
Figure 20.1
NOTE:
Check clearances carefully for this type of
installation to ensure adequate room for outside
air venting.
NOTE:
In Canada, only a full reline is allowed per
ULC
S628-93, ORD ULC C1482-M1990
.
NOTE:
In Canada this fireplace insert must be installed
with a continuous chimney liner extending from
the fireplace insert to the top of the chimney.
The chimney liner must conform to the Class
3 requirements of
CAN/ULC-S635, Standard
for Lining Systems for Existing Masonry or
Factory-Built Chimneys and Vents, or CAN/
ULC-S640, Standard for Lining Systems for
New Masonry Chimneys
.
Outside Air Pipe
Outside Air
Termination at
Chimney Top
12” (305mm)
min. below
12” (305mm)
min. above
NOTE: Use metal
plate around
exhaust vent pipe
and seal all edges
with non-flammable
insulation such as
mineral wool or
ceramic.
Do not use high
temperature caulk-
ing materials to seal
any edge to prevent
future serviceability
Check building codes prior to installation.
• Installation MUST comply with local, regional, state
and national codes and regulations.
•
Consult local building, fire officials or authorities
having jurisdiction about restrictions, installation
inspection, and permits.
CAUTION
Summary of Contents for CASTILEI-MBK-C
Page 28: ...28 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...
Page 29: ...29 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...
Page 30: ...30 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...
Page 31: ...31 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...