13
06/21
7022-801H
CASTILE INSERT
Measure and mark the metal floor for cutting. With a drill,
make a starter hole in each corner.
Figure 13.1
Using a saws-all, cut out the floor.
Keep sharp edge of
metal floor away from
power cord
Figure 13.2.
Place the insert into the factory-built firebox. Ensure that
the power cord can not be damaged by the sharp metal
edge. You may need to cut out a notch to accommodate
the cord.
NOTICE:
In Canada when using a factory-built chimney
it must be safety listed,
Type UL103 HT
(2100°F) [1149°C] CLASS “A” or conforming
to CAN/ULC-S629M, STANDARD FOR 650°C
FACTORY-BUILT CHIMNEYS
.
I. Prefabricated Metal Chimney
The chimney can be new or existing, masonry
or prefabricated and must meet the following
minimum requirements:
•
Must be minimum 6 inch (152mm) inside diameter of
high temperature chimney listed to
UL 103 HT (2100
°
F)
or ULC-S628
.
• Must use components required by the manufacturer
for installation.
• Must maintain clearances required by the manufacturer
for installation.
• Refer to manufacturers instructions for installation
• This insert is listed to
ASTM E 1509-12 Standard
and
is approved for installation into listed factory-built zero
clearance fireplaces listed to
UL 127
conforming to the
following specifications and instructions:
•
The original factory-built clearance fireplace chimney
cap must be re-installed after installing the approved
chimney liner meeting type
UL 103 HT requirements
(2100°F) per UL 1777
.
• If the chimney is not listed as meeting HT requirements,
or if the factory built fireplace was tested prior to 1998,
a full height listed chimney liner must be installed from
the appliance flue collar to the chimney top.
•
The liner must be securely attached to the insert flue
collar and the chimney top.
•
The air flow of the factory-built zero-clearance fireplace
system must not be altered. The flue liner top support
attachment must not reduce the air flow for the existing
air-cooled chimney system.
• No dilution air is allowed to enter the chimney.
a.
Secure the fireplace damper in the open position. If
this cannot be accomplished, it will be necessary to
remove the damper
b. Seal damper area of chimney around chimney
connector with a high temperature sealant or seal
insert against the face of the fireplace.
c. Both methods must be removable and replaceable
for cleaning and re-installation.
H. Installation into a Masonry Fireplace
All modifications that can be made to a Factory Built
Fireplace can be made to a Masonry Fireplace.
In addition DO NOT remove any brick or mortar from the
existing fireplace.
WARNING
•
Removing floor of fireplace must not weaken
structure of firebox or reduce protection for
combustible materials.
• Final approval of this installation type is
contingent upon the appropriate local authority
having jurisdiction.
Risk of Fire!
Follow venting manufacturer’s clearances and
instructions when installing venting system.
WARNING
Summary of Contents for CASTILEI-MBK-C
Page 28: ...28 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...
Page 29: ...29 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...
Page 30: ...30 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...
Page 31: ...31 06 21 7022 801H CASTILE INSERT Date of Service Performed By Description of Service ...