19
06/21
7022-801H
CASTILE INSERT
NOTE:
In Canada, where passage through a wall or
partition of combustible construction is desired,
the installation shall conform to
CAN/CSA-B365
.
NOTE:
•
Illustrations reflect typical installations and are FOR
DESIGN PURPOSES ONLY.
• Illustrations/diagrams are not drawn to scale.
• Actual installation may vary due to individual
design preference.
Figure 19.1
Outside Air through Rear
Wall (Horizontal)
NOTE; Use metal plate around
exhaust vent pipe and seal all
edges with non-flammable insu-
lation such as , mineral wool or
ceramic.
Do not use high temperature
caulking materials to seal any
edge to prevent future service-
ability.
C. Full Reline With Outside Air - Horizontal
Fire Risk.
Inspection of Chimney:
• Masonry chimney must be in
good condition.
• Meets minimum standard of
NFPA 211
•
Factory-built chimney must be a minimum
6 inch (152mm)
UL103 HT
.
WARNING
CAUTION
Never draw outside combustion air from:
•
Wall, floor or ceiling cavity
• Enclosed space such as an attic or garage
Summary of Contents for CASTILEI-MBK-C