15
February 19, 2020
7037-801B
C. Clearances to Combustibles
BACKWALL / SIDEWALL
A
B
D
C
CORNER INSTALLATION
F
E
E
F
ALCOVE SIDE VIEW
G
A
G
H
90° OFF TOP UP
& OUT CEILING
CLEARANCE
STOVE TO
CEILING
CLEARANCE
* If H = N/A, follow Pipe
Manufacturer’s clearances
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS in inches (Millimeters)
NOTE:
A, C, and F Dimensions are to the center of the fl ue collar
43M-ACC-C AND 43ST-ACC-C WOOD APPLIANCE (2020)
A
B
C
D
E
F
G
H
INSTALLATION: FULL VERTICAL OR HORIZONTAL WITH MINIMUM 2 FOOT VERTICAL OFF STOVE TOP
SINGLE WALL PIPE
43M-ACC-C
18-1/2 (470)
11-3/4 (298)
27-1/2 (699)
14-1/2 (368)
8 (203)
20-1/2 (521)
53-1/2 (1359)
12 (305)
43ST-ACC-C
18-1/2 (470)
11-3/4 (298)
27-1/2 (699)
14-1/2 (368)
2-1/2 (64)
15 (381)
49-1/2 (1257)
12 (305)
DOUBLE WALL PIPE
43M-ACC-C
12 (305)
5-1/4 (133)
27-1/2 (699)
14-1/2 (368)
8 (203)
20-1/2 (521)
53-1/2 (1359)
12 (305)
43ST-ACC-C
10-1/2 (267)
3-3/4 (95)
25 (635)
12 (305)
2-1/2 (64)
15 (381)
49-1/2 (1257)
5 (127)
INSTALLATION: 90 DEGREE ELBOW OFF TOP OF APPLIANCE THROUGH BACKWALL
DOUBLE WALL PIPE
43M-ACC-C
11-1/2 (292)
4-3/4 (121)
27-1/2 (699)
14-1/2 (368)
8 (203)
20-1/2 (521)
53-1/2 (1359)
N/A
43ST-ACC-C
10-1/2 (267)
3-3/4 (95)
22 (559)
9 (229)
2-1/2 (64)
15 (381)
49-1/2 (1257)
N/A
INSTALLATION: ALCOVE
DOUBLE WALL PIPE
43M-ACC-C
16 (406)
9-3/8 (238)
27 (686)
13-7/8 (352)
N/A
N/A
53-1/2 (1359)
12 (305)
43ST-ACC-C
10-1/2 (267)
3-3/4 (95)
25 (635)
12 (305)
N/A
N/A
49-1/2 (1257)
5 (127)
For alcove only:
Six inch diameter listed Double wall air insulated connector pipe with
UL103 HT
listed factory built Class A chimney or masonry chimney. Maximum
depth of Alcove shall be no more than 48 inches (1219mm) and the referenced alcove clearances. Canada must comply with
CAN/ULC-S269 M87
for the 650° factory built
chimney.
* FOLLOW PIPE MANUFACTURES CLEARANCES AS REQUIRED
NOTE:
Clearances may only be reduced by
means approved by the regulatory
authority having jurisdiction
NOTE: Service Space
In order to replace the tube channel assembly a
clearance of 19 inches (483mm) is required on the right
side of appliance in order to remove the tubes with
the appliance in place. If space is not available, the
appliance will have to be disconnected from the chimney
to proceed with the tube replacement.
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
•
Failure to comply may cause house fire.
WARNING
ALCOVE TOP VIEW
C
D