Page
4
AN-X-GENI
January 2008
Installation
Prevent Electrostatic Discharge
The module is sensitive to electrostatic discharge.
WARNING!
Electrostatic discharge can damage integrated circuits or
semiconductors. Follow these guidelines when you handle the module:
•
Touch a grounded object to discharge static potential
•
Do not touch the connector pins
Power
AN-X requires a DC power input of anywhere from 12 to 24 VDC.
Left to right the pins on the power connector are chassis ground, negative
voltage and positive voltage.
The chassis ground should be connected.
Power consumption internally is 250 mA @ 12VDC or 125 mA @
24VDC.
The part number for the power connector is Phoenix MSTB
2.5/3-ST-5.08
Genius Cabling and Termination
Refer to Genius I/O System and Communications User’s Manual,
GEK-90486F-1 for detailed information on Genius cabling and
installation.
The module has a 5-pin Phoenix connector for connection to the Genius
I/O network. The part number for the Genius bus connector is MSTB
2.5/5-ST-5.08