Page
36
AN-X-GENI
January 2008
sourceSBA is the serial bus address (SBA) of the module on the Genius
bus that is sending the data
destSBA is the serial bus address of the destination
length is the length of data in words
Genius bus input data is mapped as before.
Example:
A Genius bus controller at serial bus address 31 is sending 2 words of
output data to a Genius block at serial bus address 17. To map this data
to a offset 27 in a ControlLogix scheduled connection, and assign it
tagname Block17Outputs, add the following line to the DataInput section
of the connection
27, m31>17[2], Block17Outputs
ControlLogix Tags
As before, AN-X can create tags that can be imported into RSLogix 5000
to access the data.
Quick Start
Use the following steps to run the AN-X-GENI in ghost mode.
1.
Use the web interface to set the baud rate and serial bus address
2.
Connect AN-X-GENI to the Genius network.
3.
Use the web interface to perform an autoconfiguation and
automatically generate a ControlLogix configuration.
4.
Save and edit the Genius configuration file. Remove Scan from all
network devices.
5.
Save and download the modified Genius configuration file to the
AN-X-GENI.
6.
Save and edit the ControlLogix confguration file the AN-X-GENI
created when you performed the autoconfiguration. Comment out all
the DataOutput sections. Uncomment the ghost mode entries it
created and modify them to suit your application.
7.
Save and download the modified ControlLogix configuration file.
8.
Use the web interface to view the active configuration and locate the
data.
9.
Use the web interface to export the tags for the ControlLogix
configuration and import them into RSLogix 5000.
10.
Use the tags to access the data from RSLogix 5000.
Summary of Contents for AN-X-GENI
Page 59: ...AN X GENI Page 55 January 2008...