Genius Network Configuration
Before you can scan a Genius I/O network, you must set the AN-X
module’s serial bus address and baud rate and configure the network in
the AN-X-GENI.
Set the baud rate and serial bus address before connecting to the Genius
network.
Setting the Bus Address and Baud Rate
From the AN-X web interface, select Automation Network/Genius
Baud/Node Settings.
Check the desired baud rate from the four supported baud rates:
38.4Kbps, 76.8 Kbps, 153.6 KBPS standard or 153.6 Kbps extended.
Enter the serial bus address (SBA) for the AN-X, in the range 1 to 31.
Click the Submit Changes button to set the Genius bus properties of the
AN-X-GENI.