QSK USKI-5 Instructions Manual Download Page 9

USKI-5 Universal Sequencer & Keying Interface 

 

© Copyright 2015 QSK, llc 

www.qskllc.com 

Page 8 

 

the  last  sequence  has  completed  thereby  missing  the  beginning  of  the  next  symbol.  The  time 
duration  of  one  “unit”  in  milliseconds  (length  of  one  “dit”  or  space  between  symbols  within  a 
letter for normal weighting) is given by the formula 

T

unit

 = 

1200

𝑊𝑃𝑀

 ms 

where  WPM  is  the  code  speed  in  Words  Per  Minute.  Since  the  time  between  two  sequential 
symbols within a letter is one unit, it is necessary for the sum of all START and END delays to 
be less than the duration of one unit. As an example, for operation up to 50 WPM, the sum of 
START and END delays must be less than 24 ms.

 

USKI-5 PREPARATION FOR USE

 

The USKI-5 is shipped without the output relays installed. Remove the four #1 Pozidriv screws 
(a number #1 Phillips driver can be used with care) from either the front or rear panel and slide 
out the circuit board. Install the desired relays into the sockets labeled RY1 through RY5. Make 
sure of the relay orientation is as shown in figure 5. Pin #1 of each relay is indicated by a dot.  If 
relays  are  being  used  of  different  voltage/current  ratings,  make  sure  they  are  installed  in  the 
correct channel positions. 

 

FIGURE 5 

It  is  a  good  idea  to  make  note  of  what  relay  types  are  used  and  in  which  channels  they  are 
installed. When all relays are in place, reassemble the sequencer.

 

Summary of Contents for USKI-5

Page 1: ...QSK llc USKI 5 Universal Sequencer and Keying Interface Rev D...

Page 2: ...bit capability Non volatile memory Five output channels four input control channels Delays programmable from zero to minutes and more in 1 ms steps Silent high speed opto isolated solid state relay co...

Page 3: ...r inverted normally closed operation Once programmed the USKI 5 can be operated with or without connection to the programming computer The stored program is nonvolatile and no backup batteries are req...

Page 4: ...ter begins the attack portion of a symbol and must remain on until after decay is complete This same principal also applies to any power amplifier or antenna switching that may occur along with transm...

Page 5: ...upt is activated transmitting will be inhibited regardless of the state of other inputs If the program has already begun the transmitting sequence an interrupt condition will cause the program to imme...

Page 6: ..._3 the program will immediately switch off OUTPUT 3 disregarding the time remaining of TX_START_DEL_3 and will continue by switching off OUTPUT 2 and 1 in sequence with delays TX_END_DEL_2 and TX_END_...

Page 7: ...nction Several station configurations are suitable for control with Program C Probably the most common is shown in figure 3 the order of connections for outputs 1 4 may be different depending on the s...

Page 8: ...me to be on the safe side The user is responsible for correct programming and use of the USKI 5 sequencer During normal receive transmit receive sequencing the transmitter will be the last device to b...

Page 9: ...operation up to 50 WPM the sum of START and END delays must be less than 24 ms USKI 5 PREPARATION FOR USE The USKI 5 is shipped without the output relays installed Remove the four 1 Pozidriv screws a...

Page 10: ...t File Save As and add the extension bas to the file name as indicated below and then select Save The file will be saved with the proper extension Connect the sequencer to the computer with the USB ca...

Page 11: ...e called CW_START_DEL PTT_START_DEL or TX_START_DEL for example It may be helpful to first fill out a timing delay work sheet shown in the notes section at the end of this document Change the START an...

Page 12: ...gram they may include cwstart cwend pttstart pttend txstart or txstend routines For any inverted channel change high to low in the start routines of the program and low to high in the end routines of...

Page 13: ...g input devices connected to the sequencer and without the outputs connected to the station equipment Once the correct relative sequencing has been confirmed the sequencer can be reprogrammed with the...

Page 14: ...g delays Remember that for Programs A B or C the sequence will progress from left to right for the start delays and from the right to the left for the end delays For the output connections shown in pr...

Page 15: ...t to be on the safe side it is the first device switched off or out of circuit In this example it is assumed that there are mechanical relays which do this switching and transition in 10 ms In case th...

Page 16: ...CW mode particularly QSK operation Since transmitter PTT is not connected to the sequencer this allows for up to five other external devices to be controlled This example is for a station with separat...

Page 17: ...ch CW symbol envelope before turning off the VFO If the VFO turns off its RF output quickly the RX mute end delay can be set to zero If not and sometimes for cleaner sounding QSK operation sometimes a...

Page 18: ...RING 5 C 2 OUTPUTS OUTPUT NUMBER 14M2 PIN NUMBER PIN PROGRAM DESIGNATION 1 12 B 1 2 11 B 2 3 10 B 3 4 9 B 4 5 8 B 5 USEFUL INFORMATION Enhanced switching capabilities over what is possible with the st...

Reviews: