OPTIONS
DESCRIPTION
4 = Flush Valve
Relay will
energise
“
ON
” when Flush condition is in effect
and goes off when Flush condition is cleared. A relay being
used for Flush Valve/Pump must be assigned to one of the
main pumps in use. Flush relay
Alarm ID
(P2
1
2, 2
2
2, 2
3
2,
2
4
2, 2
5
2, 2
6
2) is used to enter the
relay number
, to which
the assigned pump is connected.
Flush Valve/Pump relay requires three setpoints. The first set
point (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3) determines the
Flush
Interval
, which is the number of main
pump cycles
that
should occur before the Flush Valve/Pump operates. The
second setpoint (P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4), sets the
number of
Flush cycles
the
Flush Valve/Pump will operate
for. This means that the Flush Valve will be operated for
several main pump starts (
Flush Cycles
) after which the Flush
Valve activity will cease until the
Flush Interval
comes
around again. Setpoint three of the Flush Valve/Pump relay
sets the
Flush Duration
, (P2
1
5, 2
2
5, 2
3
5, 2
4
5, 2
3
5, 2
3
6) this
is the duration for Flush
5 = Step Time
Step Time Control allows relays to be used to control a
device, such as a motorised valve or gate, in order to
maintain the level within two predetermined points. Relays
will
energise
“
ON
” when Step Time condition is in effect and
de-energises
“
OFF
” when Step Time goes off. One relay
will
be required to control an increase in level, (‘open’ the device)
and a second relay is required to control a decrease in level,
(‘close’ the device).
Alarm ID
(P2
1
2, 2
2
2, 2
3
2, 2
4
2, 2
5
2, 2
6
2)
is used to assign the relay to control either the
open
or
close
condition. Step Time Control relay requires three setpoints.
The first set point (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3) determines
the
level
, at which the relay is to be activated, (N.B. level
setpoint for
open
relay,
increase
the level, must be
lower
than
the setpoint for the
close
relay,
decrease
the level). The
relay will
energise
“
ON
” after the
Limit time
that is set in
Relay
Setpoint 3
(P2
1
5, 2
2
5, 2
3
5, 2
4
5, 2
5
5, 2
6
5). And turns
“
OFF
”,
de-energises
, after the
Drive Period
that is set in
Relay
Setpoint 2
(P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4).