PULSAR MEASUREMENT
139
Stability Parameters
Damping
Damping is used to damp the display, to enable it to keep up with the
process but ignore minor surface fluctuations.
P870 Fill Damping
This parameter determines the
maximum rate
at which the unit will
respond to an
increase in level
. It should be set slightly higher than the
maximum vessel fill rate.
Default = 10m/min.
P871 Empty Damping
This parameter determines the
maximum rate
at which the unit will
respond to a
decrease in level
. It should be set slightly higher than the
maximum vessel empty rate.
Default = 10m/min.
Indicator
P872 Fill Indicator
This parameter determines the rate at which the LCD
fill
indicator activates.
Default = 10m/min.
P873 Empty Indicator
This parameter determines the rate at which the LCD
empty
indicator
activates.
10m/min.
Rate
P874 Rate Update
This parameter determines the way in which the rate is calculated. If set to
continuous
(
P874
=
0
), then the rate is calculated and displayed
continuously, i.e. any change seen from shot to shot is calculated and
displayed, but if set to use
values
P874
=
1(Default)
then the
values
set in
P875
and
P876
are used to calculate and display the rate.
P875 Rate Time
This parameter is the period (in seconds) over which the material level rate
of change is averaged before the
Rate
Value
(
P877
) is updated. If the
Rate
Distance
(
P876
) is exceeded before the
Rate Time
(
P875
) has expired, then
the
Rate Value
(
P877
) will be updated immediately.
Default = 60sec.