ZENITH 140
INSTRUCTION MANUAL
142
P902 Echo Strength 1
This parameter displays the most recent echo strength figure for the
transducer, where a higher figure indicates a better returned echo.
P903 Average Noise 1
This is the mean noise reading for the transducer. It is measured while the
transducer is not firing and gives an indication of the average amount of
electrical noise present on the cabling.
P904 Peak Noise 1
This is the peak noise reading for the transducer. It is measured while the
transducer is not firing and gives an indication of the maximum amount of
electrical noise present on the cabling.
P905 Sensitivity 1
This parameter determines the sensitivity of the unit. Please consult Pulsar
for further information and assistance on changing the value of this
parameter.
P906 Side Clearance 1
This parameter is used to set the distance by which the DATEM trace will
“stand
-
off” from around unwanted echoes such as obstructions. Please
consult Pulsar for further information and assistance on changing the value
of this parameter.
Transducer 2 Status
P910 - 916 Transducer 2
These parameters contain the same information as detailed in Transducer 1
Status, for Transducer 2.