PULSAR MEASUREMENT
87
P211, 221, 231, 241, 251, 261 =3 (Aeration)
Relay Setpoints are entered in Minutes to set Time Period that the relay will
remain ON.
See the appropriate relay Function tables (
P211, 221, 231, 241, 251, 261
)
for further information.
P211, 221, 231, 241, 251, 261 =4 (Flush Valve)
Relay Setpoints are entered in cycles to set the number of Flush cycles.
See the appropriate relay Function tables (
P211, 221, 231, 241, 251, 261
)
for further information.
P211, 221, 231, 241, 251, 261 =5 (Step Time)
Relay Setpoints are entered in Seconds to set
Drive Period
, the time that
the relay will remain ON
See the appropriate relay
Function
tables (
P211
,
221
,
231
,
241
,
251, 261
)
for further information.
P211, 221, 231, 241, 251, 261 =6 (Differential)
Relay Setpoints are entered in values of Measurement Units (P104).
See the appropriate relay Function tables (
P211, 221, 231, 241, 251, 261
)
for further information.
P215, P225, P235, P245, P255, 265 Relay Setpoint 3
P211, 221, 231, 241, 251, 261 = 4 (Flush Valve)
Enter desired
Flush duration
in seconds.
See the appropriate relay Function tables (
P211, 221, 231, 241, 251
) for
further information.
P211, 221, 231, 241, 251, 261 = 5 (Step Time)
This parameter is used to determine the Limit Time between each Drive
Period. Relay Setpoints are entered in Minutes, during which time the relay
will remain OFF.
See the appropriate relay Function tables (
P211, 221, 231, 241, 251, 261
)
for further information.