![Pulsar UltraTWIN Instruction Manual Download Page 187](http://html1.mh-extra.com/html/pulsar/ultratwin/ultratwin_instruction-manual_1624516187.webp)
PULSAR MEASUREMENT
187
mA2 Limits
P1 and P2
P*894 mA2 Low Limit
This parameter sets the lowest level that the mA output will drop to, the
default is 0mA, but you can override this if the device you connect to cannot
for example accept less than 2mA, yet you want to use the 0-20mA range.
Default = 0.00mA
P*895 mA2 High Limit
This parameter sets the highest level that the mA output will rise to, the
default is 20 mA, but you can override this if the device you connect to
cannot for example accept more than 18 mA, yet you want to use the 0-20
mA range.
Default = 20.00mA
mA2 Trim
P1 and P2
P*896 mA2 Low Trim
If the device you are connected to is not calibrated, and not showing the
correct
low value
(reading), then you can trim it using this parameter. You
can either type in the offset directly or use the arrow keys to move the
output up and down until you get the expected result (reading) on the
device that is connected.
P*897 mA2 High Trim
If the device you are connected to is not calibrated, and not showing the
correct
high value
(reading), then you can trim it using this parameter. You
can either type in the offset directly or use the arrow keys to move the
output up and down until you get the expected result (reading) on the
device that is connected.