ULTRATWIN (UL)
INSTRUCTION MANUAL
134
P*211, 221, 231, 241, 251, 261 =3 (General Control)
Relay Setpoint 1 is entered in values of Measurement Units (P*104)
See the appropriate relay function tables (
P*211, 221, 231, 241, 251, 261
)
for further information.
P*214, P224, P234, P244, P254 Relay Setpoint 2
P211, 221, 231, 241, 251, 261 =1 (Time)
This parameter determines the “Cycle Time” for the operation of the relay.
See the appropriate relay Function tables (
P211, 221, 231, 241, 251, 261
)
for further information.
P211, 221, 231, 241, 251, 261 =2 (Storm)
Relay Setpoints are entered in values of Measurement Units (P104)
See the appropriate relay Function tables (
P211, 221, 231, 241, 251, 261
)
for further information.
When P*211, 221, 231, 241, 251, 261 =3 (General Control)
This parameter determines the “OFF” point of the relay
.
Relay Setpoints are entered in values of
Measurement Units (P*104)
See the appropriate relay
Function
tables
(P2*11, 221, 231, 241, 251, 261)
for further information.
P*215, P*225, P*235, P*245, P*255, P*265 Relay Setpoint 3
When P*211, 221, 231, 241, 251, 261 = 2 (Step Time)
This parameter is used to determine the Limit Time between each Drive
Period. Relay Setpoints are entered in Minutes, during which time the relay
will remain OFF.
See the appropriate relay
Function
tables
(P*211, 221, 231, 241, 251, 261)
for further information.
When P*211, 221, 231, 241, 251, 261 = 1 Time or 3 (General Control)
This parameter has no function and will not be displayed.
P*216, P*226, P*236, P*246, P*256, P*266 - Relay Allocation
When P*211, 221, 231, 241, 251, 261 = 1 (Time)
This parameter has no function and will not be displayed.