PT113
Instruction Manual
52
Ethernet/IP Data Structure
The data format of the weight value can be read as Floating point (IEEE 754) or Integer.
PT113EI Output to PLC Input
Communication consists of a message 3 Dwords in length.
Bitwise order of a Dword:
Dword
(Read)
D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
D15 D14 D13 D12 D11 D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
1
st
Dword
Not
Used
2
nd
Dword
By default, Indicated weight value is represented.
To represent other weight or calibration status, refer to the next Dword.
3
rd
Dword
PT113EI Error codes
Op.
mode
Zero
range
Gross
Net
MD
Read command response
Cmd
Flg
PT113EI Output to PLC Input 3
rd
Dword
Bit Number
3
rd
Dword Description
D31 … D16
Not in use
D15 … D12
Error Codes of
the PT113EI
Bin
Dec
0000
0
No error found
0001
1
ADC out
0010
2
ADC over
0011
3
ADC under
0100
4
System Error
0101
5
In programming mode
0110
6
Low/High Voltage Error
01111
7
Instrument cannot be found
D11 … D10
Not in use
D9
Operating
Mode
0
Weight or Force mode
1
Count Mode
D8
Centre of zero
0
Weight is out of centre of zero range
1
Weight is in centre of zero range
D7
Indication
0
Gross
1
Net
D6
MD – Motion
Detection
0
Stable
1
Dynamic
D5 … D1
Read
Command
Response
00000
0
Indicated weight (Gross or Net) as 32 bit integer
00001
1
Gross weight as 32 bit integer
00010
2
Tare weight as 32 bit integer
00011
3
Indicated weight (Gross or Net) as Floating point
00100
4
Gross weight as Floating point
00101
5
Tare weight as Floating point
00110 -
01111
6 - 15 Not used
10000
16
Calibration Status (refer below)
D0
CMD Flag
Toggles
The command is applied successfully