PT113
Instruction Manual
13
LINK/Activity LED
LED State
Description
Comment
Off
No Link, no activity
No link, no communication present
Green
Link
Ethernet 100 Mbit/s link established,
no communication present
Green,
flickering
Activity
Ethernet 100 Mbit/s link established,
communication present
Yellow
Link
Ethernet 10 Mbit/s link established,
no communication present
Yellow,
flickering
Activity
Ethernet 10 Mbit/s link established,
communication present
NS Network Status LED
LED State
Description
Comment
Off
IP address not assigned/set
Check IP address setting
Green
On-line (RUN)
One or more connections
established (CIP Class 1 or 3)
Green, flashing
Online, no connections established
Red
Duplicate IP address, FATAL error
Red, flashing
One or more connections timed out (CIP
Class 1 or 3)
5.1.2.6 PT113CO
The PT113CO has 2 additional LEDs, Error and Run, above and below the CANopen connector
respectively, with meanings as below.
Run LED
State
Indication
Comment
Off
Not online /No power
Check power and cable
Green
On-line, data exchange
-
Green, blinking
On-line, initializing
-
Green, single flash
Stopped
Check hardware for damage
Green, flickering
Auto baudrate detection in
progress
-
Red
CANopen configuration error
Check EDS file
Error LED
State
Indication
Comment
Off
-
No power or CANopen module is in
the initialisation state
Red, single flash
Warning limit reached
A bus error counter reached or
exceeded its warning level
Red, flickering
LSS
LSS services in progress
Red, double flash
Error count event
A guard- (NMT-Slave or NMT-
master) or heartbeat event
(Heartbeat consumer) has occurred.
Red
Bus off (Fatal Event)
Bus off.