31
13.0 Technical Specifications
The following technical specifications are important and vital to the correct operation of the
Protégé® SE Integrated System Controller. Failure to adhere to the technical specifications will
result in any warranty or guarantee that was provided becoming
NULL AND VOID.
Integrated Control Technology continually strives to increase the performance of its products and
as a result the specifications may change without notice.
It is recommended that you always
consult www.incontrol.co.nz for the latest documentation and product information.
Operating Voltage
15.5 to 16.5VAC, 50-60Hz @ 40VA (Max)
Operating Current
280mA (Typical)
Total Combined Current
1.8A (Max)
DC Output (Auxiliary)
700mA (Typical) 1.1A (Max) Electronic Shutdown at 1.1A
B1/B2 DC Outputs (Continuous)
8 Ohm 20W Siren or 700mA (Typical)
B1/B2 DC Outputs (Inrush)
1000mA
Battery Charging
350mA/700mA
Battery Low
11.2VDC
Battery Restore
12.5VDC
Electronic Disconnection
8.76VDC
Communication (Ethernet)
1x 10/100Mbps Ethernet Communication Link
Communication (Serial)
1x Isolated RS-485 Communication Interface Port 12VDC @ 28mA. (Input)
Communication (Modem)
1x 2400bps Modem Communication
Readers (Standard Mode)
2x Wiegand or clock data readers providing one Entry/Exit Door or two
Entry/Exit only Doors.
Readers (Multiplex-reader Mode)
4x Wiegand Readers (connected in Multiplex Reader mode) providing any
combination of Entry or Exit for two Doors.
Zone Inputs (System Zones)
16x High Security Monitored Zone Inputs
Tamper Input
Dedicated Hardware Tamper Input
PGM Outputs
6x 50mA (Max) Open Collector Output for reader LED and beeper or general
functions.
Status Output
1x 50mA (Max) Open Collector Output
Operating Temperature
0˚ to 55˚C (41˚ to 131˚F)
Storage Temperature
10˚ to 85˚C (14˚ to 185˚F)
Humidity
0% to 85% (non condensing)
Dimensions (L x W x H)
234 x 183 x 35mm (9.21 x 7.20 x 1.37”)
Weight
790g (27.86oz)
The size of conductor used for the supply of all power to the Protégé® SE Integrated System Controller should be
adequate in size to prevent voltage drop at the terminals of no more than 5% of the rated voltage. Specifications are
subject to change without notice, please visit www.incontrol.co.nz for updated information.
!
The total combined current including operating current, charging current, DC
Output (Auxiliary), B1 and B2 must be limited to a maximum of 1.8A.