18
5.5 Programming the Onboard Reader
The onboard reader is programmed in exactly the same way as any other reader module is. It can
be though of as if it were a normal reader expander module on a separate circuit board. By default
the onboard reader is registered as the last reader in the defined profile (which is Reader Expander
008 in the Standard Profile). Consequently any reader expander module that is connected with the
same address as this will be treated as a duplicate and will fail to register. To change the address at
which the onboard reader is registered, or to disable it please refer to the Protégé® SE Integrated
System Controller Programming Guide.
The onboard reader uses zone inputs 9-12 and 13-16 as it’s door contact, REX, bond sense and REN
inputs respectively. Any of these inputs that are not configured for use with the Onboard Reader
may be used as general purpose zone inputs. The default settings are shown in the following table:
To enable or disable the onboard reader inputs use the reader expander properties box in the
Protégé® Software as shown below.
Figure 20 - Reader Expander Properties Box
Zone
Access Control Function
Default Setting
Zone 9
Door Contact, Port 1
Door Contact, Port 1
Zone 10
REX Input, Port 1
REX Input, Port 1
Zone 11
Bond Sense, Port 1
General Purpose Zone
Zone 12
REN Input, Port 1
General Purpose Zone
Zone 13
Door Contact, Port 2
Door Contact, Port 2
Zone 14
REX Input, Port 2
REX Input, Port 2
Zone 15
Bond Sense, Port 2
General Purpose Zone
Zone 16
REN Input, Port 2
General Purpose Zone