25
Complete Operating Menu / Description
Feed forward control
Standard signal output 1
feed forward ctrl.
Hz / mA
10 Hz
D1C2-cond.-035-GB
feed forward ctrl.
setting ?
max. additive
feed forward ctrl.
regulated value
10.00 Hz
effect:
feed forward ctrl.
additive
100 %
feed forward ctrl.:
rated value:
D1C2-cond.-027-GB
0…20 mA
0 mA =
20 mA =
0%
0 mA =
20 mA =
100%
➞➞
positive cond
negative cond
Access to all setting menus can be blocked with an access code !
Control with standard signal
mA output 1 PS1
setting ?
only with standard signal output
mA output 1
control
regulated value:
mA output 1
regulated value
measured value
mA output 1
measured value
mA output 1
100.0
°
C
0 mA =
20 mA =
correction value
0.0
°
C
0,0 mS/cm
200.0 mS/cm
Possible values
Initial value
Increment
Lower value
Upper value
Remarks
Feed forward control
as per
none
Signal processing:
(flow)
identity code at
10 Hz
Signal < 0,2 mA = No flow
standard signal
500 Hz
Signal < 4,2 mA = No flow
0...20 mA
4...20 mA
Feed forward control
20 mA
0.01 mA
0/4 mA
20 mA
Depending on signal type.
rated value
10 Hz
0.01 Hz
0.1 Hz
10 Hz
Maximum limitation of
500 Hz
1 Hz
5 Hz
500 Hz
range used.
Feed forward control
multiplicative
multiplicative
Feed forward effect
additive
Max. additive regulated
100 %
1 %
-500 %
+500 %
Only with additive
value
regulated value.
BA_DM_138_09_06_GB.p65
21.09.2006, 11:22 Uhr
25