Actuating variable for ORP raising agent
Measured value of mA output, temperature
6.4 Configuring the mA outputs
Parameters for mA outputs
OFF
System overview
2021-06-22
14:21:28
START 1
assigned value at 0/4 mA
A3195
assigned value at 20 mA
Range
Current with error
0.00 pH
12.00 pH
0 - 20 mA
23 mA
Fig. 10: Configuring mA outputs
As shown in
Chapter 6.3 ‘mA outputs 1 ... 4’ on page 20, a cur‐
rent corresponding to a set actuating variable, and a measured
value for pH / ORP / chlorine / combined chlorine and temperature
can be provided at the mA output.
1.
The current output is not set up in the module but in a sub-
menu of the respective measuring channel. To do so, switch
to the tile view of the measured values in the DULCO‐
MARIN
®
3 and select the corresponding measured value.
2.
The
‘Output’ menu is located in the sub-menu of the meas‐
uring channel to parametrise the current output.
Parameter
Function
Assigned value at 0/4 mA
The corresponding lower measured value for the current interface is
specified here.
Assigned value at 20 mA
The corresponding upper measured value for the current interface is
specified here.
Range 0 ... 20 mA
Current interface with 0 ... 20 mA (errors with 23 mA can be displayed in
the upper range).
Range 4 ... 20 mA
Current interface with 4 ... 20 mA (errors with 3.6 mA can be displayed
in the lower range).
Current with error OFF
In the event of a fault, 0 mA is emitted as the corresponding current.
Caution: the current continues to be issued as the measured value with
current output settings on the IO module board.
Current with error 3.6 mA
In the event of an error with the measured value in the swimming pool,
3.6 mA is emitted at the current interface.
Current with error 23 mA
In the event of an error with the measured value in the swimming pool,
23 mA is emitted at the current interface.
Configuring the A-module (DXMaA) (actuator module)
21