![promesstec UMU 100-A-B User Manual Download Page 55](http://html.mh-extra.com/html/promesstec/umu-100-a-b/umu-100-a-b_user-manual_1616639055.webp)
55
promesstec GmbH
I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: [email protected] I Internet: www.promesstec.com
11. Visualisation in the UMU-FD
Sensor error detection and input signal outside range
Sensor error check:
Device
Configuration
Sensor error detection:
UMU 100
R1, ERR.ACT=NONE - R2,
ERR.ACT=NONE,
OUT.ERR=NONE
OFF
Else:
ON
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Input
Range
Readout
Limit
VOLT
0…1 V / 0,2…1 V
IN.LO
< -25 mV
IN.HI
> 1,2 V
0…10 V / 2…10 V
IN.LO
< - 25 mV
IN.HI
>12 V
CURR
0…20 mA / 4…20 mA
IN.LO
< -1,05mA
IN.HI
>25,05 mA
LIN.R
0…800 Ω
IN.LO
< 0
Ω
IN.HI
> 1075
Ω
0…10 kΩ
IN.LO
< 0
Ω
IN.HI
>110 k
Ω
POTM
-
IN.LO
< -0,5 %
IN.HI
>100,5 %
TEMP
TC /RTD
IN.LO
< temperature range -2°C
IN.HI
> temperature range +2°C
Display redout below min. /above max. (-1999, 9999):
Input
Range
Readout
Limit
All
All
-1999
Display readout <-1999
9999
Display readout >9999
Sensor error detection limits
Sensor error detection (SE.BR, SE.SH)
Input
Range
Readout
Limit
CURR
Loop break (4…20mA)
SE.BR
<=3,6 mA; >= 21 mA
POTM
All, SE.BR on all 3-wire
SE.BR
> ca. 126 k
Ω
LIN.R
0…800Ω
SE.BR
> ca. 875
Ω
0…10kΩ
SE.BR
> ca. 11 k
Ω
TEMP
TC
SE.BR
> ca. 750 k
Ω / (1.25V)
RTD, 2-, 3-, and 4-wire
NoSE.SH for Cuxx, Pt10, Pt20 and
Pt50
SE.BR
> ca. 15 k
Ω
SE.SH
< ca. 15
Ω