Ext. Fan:
It indicates ambient temperature setting to switch on the external
fan. The default value is 25°C.
Bat Low Volt
▼
Charger I
Backup Timer
Default UPS
Bat. Low Volt:
It’s allowed to set the low battery warning voltage. The
resettable range is 42.0~55.0V. The default value is 46V.
Charger I:
It’s to configure the charger current. There are 2, 4, 6, 8 or 10Amp
for selection. The default value is 10A.
Backup Timer:
It’s to configure the warning time for backup time. This
function is available only when timer is set in dry contact. The adjustable range
is 0~480 min with 15-min increment of each click by pressing SCROLL button.
The default value is 120min.
Default UPS:
Restore factory settings of UPS.
Default SNMP
Test Timer
Set Date/Time
Password
▲
Default SNMP:
Restore factory settings of SNMP.
Test Timer:
It’s to define the time of Self-Test. The adjustable range is
1~255min.
Set Date/Time:
It indicates setting for date and time.
Password:
The Password to access Setting and Control Menu can be changed
here. Use the SCROLL key with ENTER keys to enter a correct Password.
Re-entry is required if an error occurs when entering the password.
5.5.10
Control menu
Press SCROLL button to switch desired option in Control menu and press ENTER button to confirm new option.
Pressing ESC button will return to default page.
Control page
Explanation
Self Test:
⊙
Start
○
Stop
Starts the Self Test.
CAUTION:
The unit must be in Normal, Boost or Buck Mode before starting
the self-test.
Dry Test:
⊙
On
○
Off
○
Cancel
Starts the dry contact test.
-
On: All dry contacts are energized. This action will be finished
automatically after 1 minute.
-
Off: All dry contacts are ineffective. This action will be finished
automatically after 1 minute.
-
Cancel: Cancel this test immediately.
Ext Fan Test:
⊙
On
○
Off
○
Cancel
Starts the external fan test.
-
On: The external fan has power from battery. This action will be finished
automatically after 1 minute.
-
Off: Cut off battery power. This action will be finished automatically after 1
minute.
-
Cancel: Cancel this test.
UPS Output:
⊙
On
○
Off
UPS output can be turned ON or OFF. This option is available when the UPS is
in INV, Boost, Buck or Normal Mode.
Reset Event/TM?
⊙
Yes
○
No
It resets all event numbers and time duration to zero.
5.5.11
Help menu
It shows UPS model name in Help menu.
Help page
Explanation
Indicates UPS model name.
UPS-2000A