6. SPECIFICATIONS
6.1
Line Mode Specifications
Rated Power
2000VA/1600W
Power factor
0.8
Nominal battery voltage
48Vdc
Utility Voltage Waveform
Sinusoidal (utility or generator)
Utility qualify time setting
3/10/30 seconds adjustable,
Nominal Input Voltage
120Vac or 230/240Vac
AVR function
Enable/ Disable
Utility voltage range
88 ~152 Vac or 176 ~ 300Vac user programmable.
Defaults set @ 100 ~ 130Vac or 200 ~ 260Vac
Nominal Input Frequency
50Hz / 60Hz (Auto detection, 55Hz as boundary)
Default frequency
Last utility frequency
Utility frequency range
47 ~ 53 Hz(50Hz mode) / 57 ~ 63Hz(60Hz mode)
Transfer Time
UPS without PTS
Normal mode
12ms maximum
Generator mode
25ms maximum
UPS with PTS
40ms maximum
Overload Protection
5s@≥125 ~150% load; 60s@110%~125% load
Output short circuit
Input/Output Breaker
Site fault detection
Yes
Efficiency (Line mode)
95%
Efficiency (AVR mode)
90%
External PTS power capacity
30A
External PTS
When UPS is good, the PTS allows UPS output to flow out to the outdoor
cabinet
If the UPS is not functioning, the PTS will bypass the UPS allowing the
utility to flow out to the outdoor cabinet.