10
• To avoid the dangers of fire, electric hazards and equipment damage, be sure to use
only the specified voltage when operating the FP.
• Since there is no power switch on the FP unit, be sure to attach a breaker-type switch
to its power cord.
Electrical Specification
Environmental Specification
Power Cable Connecting
Connecting the FP Power Cord
(1) Be sure that the FP’s power cord is not plugged in to the power supply.
(2) Remove the Terminal Strip’s clear plastic cover.
Item
Specification
P
o
wer Supply
Input Voltage
AC100 ~ 240V
Rated Voltage
AC85V ~ AC265V
Rated Frequency
50 / 60HZ
Allowable Frequency Range
40Hz - 72Hz
Allowable Voltage Drop
1 cycle (Max.)
Current Consumption
AC100V 0.9A or less (TYP0.55 A)
AC240V 0.45A or less (TYP0.30 A)
In-Rush Current
60A (Max.)
Voltage Endurance
AC1500V 20mA for 1 minute
(between charging and FG terminals)
Insuration Resistance
DC500V 10M
Ω
(Min.)
(between charging and FG terminals)
Item
Specification
Surrounding Air
Temperature
0~50ºC (The panel should not incline more than 30º)
Storage Temperature -20 ~ +60ºC
Ambient Humidity
10~90%RH
(No condensation, Wet bulb temperature: 39ºC max.)
Storage Humidity
Air Purity (Dust)
0.1mg/m
3
(Max.) (No electrically conductive dust is allowed)
Pollution Degree
Pollution Degree 2
AC cable
Grounding Wire
Power Cord
Double insulation wire
1.25~2.0 mm
2
[0.0024inch
2
to 0.0062 inch
2
]
(16-14AWG)
1.25~2.0 mm
2
[0.0024inch
2
to 0.0062 inch
2
]
(16-14AWG)
Recomended Ring
terminal
*1
*1.
In order to prevent a short circuit caused by loose screws, make sure to use a
crimp-type terminal with insulating sleeve.
V2-MS3 compatible
(J.S.T. Mfg. Co.,Ltd).
Over ø3.2 mm[0.13 in.]
V2-P4 compatible
(J.S.T. Mfg. Co.,Ltd).
Over ø4.3 mm[0.17 in.]
Under 6.0 mm
[0.24 in.]
Under 7.0 mm
[0.28 in.]