AdvAntAge - digitAl vAv diffusers
DISPLAY NAVIGATION
20
ACUTHERM ADVANTAGE - Manual
|
acutherm.com
input Menu
Supply Air Temp and Neutral Mode
Scroll through with
Up
and
Down
buttons, press
Menu
button to apply your changes *---wait---* will display as changes are applied.
serviCe Menu
inPut
suPPlY Air teMP
50.0°f
supply Air temperature (sAt) readout
· Shows current SAT reading.
· Range: -59.0°F – 300.0°F.
· No probe, means no sensor is connected.
neutrAl MOde
enABled
neutral Mode = enabled
· Uses hot/cold switch points which are hard set.
· Not recommended.
neutrAl MOde
dYnAMiC
neutral Mode = dynamic
· When supply air temp (SAT) is below room temp it is considered cooling.
· When supply air temp (SAT) is above room temp it is considered heating.
· This mode is recommended because Advantage will always use the supply air if it can help satisfy the room load.
neutral Mode = Conventional
· Uses fixed supply air temp (SAT) to switch to cooling and heating
· Hot Switch - set SAT temperature to enable heating
· Cold Switch - set SAT temperature to enable cooling
neutral Mode = force Cool
· Locks the diffuser in the cooling mode
neutral Mode = force Heat
· Locks the diffuser in the heating mode
rM.tM.Offset
0.0°f
Plaque temperature Offset
· Offsets the room temperature sensor.
· Default 0.0°F
PlAQue Offset
0.0°f
Plaque temperature Offset
· N/A
sAt Offset
0.0°f
supply Air temperature Offset
· Offset the SAT sensor
· Default 0.0°F
COntACtCl1Cfg
nO ACtiOn
Configure action of contact switch(s) 1 - 4
· When switch closed: No Action, Unoccupied mode, Occupied mode, Damper full open, Damper full closed
· Only available if optional I/O Board installed.
· Default: No Action
CO2 sensOr
nOt deteCted
requires use of lCd tstat with CO2 and Humidity sensor
· CO2 Sensor = Detected
· CO2 Tweak = 0%
· CO2 Offset = 0% APM
HuMiditYsens
nOt deteCted
requires use of lCd tstat with CO2 and Humidity sensor
· HumiditySens = Detected
· HumidityTweak = 0%
· HumidityOfset = 0% RH
PWr frQ
60 Hz
Configure supply power frequency
· 60 Hz or 50 Hz
MOtOr sWitCH
OPen
read Only
· Indicates status of motor switch
MOtOr sWitCH
COntACted
read Only
· Indicates status of last calibration
Press Menu
tO eXit
exit