AdvAntAge - digitAl vAv diffusers
DISPLAY NAVIGATION
21
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
OutPut
AuX BinArY used As:
OutPut
AuX BinArY
used As
HeAt OutPut
used As
HeAt OutPut
Heat Output (default)
· Output energized when the room demand is heating
and the heat load is at or above trip point (below)
used As
COOl OutPut
Cool Output
· Output energized when the room demand is cooling
and the cool load is at or above trip point.
used As
HeAt And COOl
Heat and Cool
· Output energized when the room demand is
heating or cooling and load is above trip point.
used As
deAdBAnd Out
deadband Output
· Output energized when room is satisfied.
used As
rOOM ligHts
room lights
· When using Motion T-Stat, output controls room lights.
used As
fOrCe Off
force Off
· Output de-energized at all times.
used As
fOrCe On
force On
· Output energized at all times.
reHeAt tYPe
On/Off
reheat type
· On/Off (default from factory)
· PWM - pulse width modulation (use SSR Relay)
· PDM - pulse delay (ON minimum of 2min) modulation (use SSR Relay)
· On/Off - HotAirDis - no heat when supply air is hot
· PWM - HotAirDis - no heat when supply air is hot
· PDM - HotAirDis - no heat when supply air is hot
Output fail safe
· Disabled = cooling 0VAC, heating 24VAC (valve open)
· Enabled = cooling 24VAC (valve closed), heating 0VAC
triP POint
5%
OutPutfAilsAfe
disABled
Press Menu
tO eXit
OutPut
AnAlOgs
See
Output Analog Menu (next page)
Press Menu
tO eXit
Output Aux Binary Menu
Scroll through with
Up
and
Down
buttons, press
Menu
button to apply your changes *---wait---* will display as changes are applied