AdvAntAge - digitAl vAv diffusers
NATIVE BACNET NETWORK INTERFACE OPTIONAL ACCESSORY
29
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
BACnet service Menu
Each controller’s MAC address, Device Instance, and Baud rate are set in the BACnet sub-menu of the service menu accessed
through an LCD thermostat or LCD setup tool. For information on how to select a MAC address and Device instance for any
controller on a network, see following pages.
To set the controller’s BACnet settings, enter the Service Menu and adjust settings as follows:
nOte:
When the screen displays a flashing value, that value is ready to be changed and can be adjusted by pressing the arrow
keys. Pressing Menu will save the value.
BACnet service Menu
Hold down the
Menu
button on the LCD Thermostat for 5
seconds
until prompted for a passcode; use and to
enter the passcode;
DOWN, UP, UP, DOWN
.
The screen will now display “Service Menu: Application.”
Scroll down to the BACnet sub-menu.
Press the
Menu
button to enter this menu.
Screen will now show ‘MAC set in Hardware’, this is a default
setting that means the physical DIP switched on the BACnet
board must be set to set the MAC address. For easier setup,
Acutherm recommends setting the MAC over software which
will override the DIP switch settings.
Use the up arrow to scroll to whatever MAC you are intending
to set this controller to, once you arrive at the number, press
Menu to save.
By default, the MAC address will appear as the last 2 digits of
the device instance.
serviCe Menu:
APPliCAtiOn
serviCe Menu:
BACnet
MAC set in:
HArdWAre
MAC Address:
sOftWAre 0
THEN
THEN
THEN
THEN
THEN
5 SECONDS