AdvAntAge - digitAl vAv diffusers

DISPLAY NAVIGATION

18

ACUTHERM ADVANTAGE - Manual 

  |   

acutherm.com

vvt Menu 

Pressure Dependent Mode

Scroll through with 

Up

 and 

Down

 buttons, press 

Menu

 button to apply your changes *---wait---* will display as changes are applied.

vvt

dPr. COOl Min* 

0%

Cool Min flow

 · Cool Min Flow in %
 · Range: 0-100% Default: 0%

dPr. COOl MAX.* 

100%

Cool Max flow

 · Cool Min Flow in %
 · Range: 0-100% Default: 100%

dPr. HeAt Min* 

0%

Heat Min flow

 · Heat Min Flow in %
 · Range 0-100% Default: 0%

dPr.HeAt MAX* 

100%

Heat Max flow

 · Heat Max Flow in %
 · Range 0-100% Default: 100%

dPr. neutrAl 

0%

neutral flow

 · Sets the neutral flow
 · Range 0-100% Default: 0%

unOCC dPr POs* 

0%

unocc dpr Pos

 · When Advantage is unoccupied damper will ‘rest’ at this position
 · Range: 0-100% Default: 0%

inlet siZe* 

10 inCHes

inlet size

 · Size of the diffuser inlet (factory set)

K fACtOr* 

1500

K factor

 · If no DMS flow option is present, item will not display
 · Air flow calibration factor see DMS manual for more details

Air flOW* 

200 cfm

Air flow Measurement

 · If no DMS flow option is present, item will not display
 · If DMS flow option is present, LCD will display air flow rate

flOW units* 

cfm

Air flow Measurement

 · If no DMS flow option is present, item will not display
 · Units of measure for air flow adjustable to ‘cfm’, ‘l/s’, or ‘cmh’

Press Menu 

tO eXit

exit –

 

This will exit the info menu if you select Yes 

Note: Info menu will automatically time out after 60 seconds

*

Also available over BACnet network if diffuser has BACnet option installed.

Summary of Contents for Acutherm Advantage Master

Page 1: ...v200 Issue Date 12 30 21 2021 Acutherm All rights reserved MANUAL INSTALLATION Advantage Advantage Digital VAV Diffusers...

Page 2: ...nformation Menu LCD Stats only 14 Service Menu LCD Stats only 15 Balancing Menu 16 VVT Menu Pressure Dependant Mode 17 Setpoint Menu Setpoint Limits and Temperature Units 18 Input Menu Supply Air Temp...

Page 3: ...ing Notify carrier if external damage exists Submit all claims for shipping damage to the carrier 2 Move diffusers in cartons to installation area Note any unit identification 3 Remove cardboard box a...

Page 4: ...unding Secondary power supply will be factory connected to pluggable 24 VAC PWR terminal block See Mounting Installation instructions on Page 9 if transformer is shipped separately 3 Advantage Power M...

Page 5: ...xtended by using a CC cable connector for longer runs A maximum of five ADVD can be supported by one Advantage Master ADVM Each ADVD draws 3 0 VA APM PPM 115 277 POWER SUPPLY ONE OUTPUT JACK MASTER CS...

Page 6: ...parameters of the diffuser NOTE When using the Room Sensor or Dial Thermostat order a LCD SET minimum of one per project to configure the diffuser Thermostat Adjustment VAV Cooling VAV Heating Connec...

Page 7: ...override open command using the menus availble on the LCD thermsotat Service Menu Balanacing Dpr Override Goto Full Open see Balancing Menu page 16 or if the Advantage is on a BACnet network setting...

Page 8: ...not specified Pulse Delay Modulation Reheat relay is on for a minimum of 2 minutes when required OFF Cycle is proportional to heating requirement Suitable for hydronic systems where entire system is...

Page 9: ...longer runs Fig 6 page 3 210ft maximum CSJ Cable Splitters used to daisy chain power between masters Fig 6 page 3 Power switch with indicator LED Installation Instructions 1 Turn off power switch Rem...

Page 10: ...r the PLD Advantage Linear Diffuser The Advantage Pressure Relief Collar PRC slips over the Advantage inlet to provide a simple and inexpensive method to control duct static pressure The PRC s dual sh...

Page 11: ...ensing All master units have a temperature sensor located near the inlet for automatic heating cooling changeover For automatic changeover the Advantage uses a dynamic neutral mode for optimal use of...

Page 12: ...ermostat is powered from the controller Measures room temperature Set point can be adjusted from a hidden dial on the back of the T Stat using a small flat head screw driver Set point limits can be ad...

Page 13: ...k The LCD Thermostat with Motion Sensor can be used as a balancing tool for the Intelligent Controller system by simply connecting the RJ 45 cable to the back of the thermostat This thermostat can als...

Page 14: ...rtion of the thermostat first and then snapping the bottom half in 3 All thermostats will come equipped with a 0 050 Allen key for the set screw at the bottom 1 25 32 Wall Fasteners by others Surface...

Page 15: ...urate flow measurement the DMS must be installed with correct alignment between diffuser DMS collar and flex elbow DIFFUSER AIR FLOW MEASUREMENT OPTION The DMS air flow measurement sensor may be added...

Page 16: ...crease push buttons for day set point adjustment DAY SETPOINT 75 0 F DAY SETPOINT SAVING CONTROLLER LCD THERMOSTAT STANDARD MODEL Displays firmware version of thermostat LCD THERMOSTAT VERSION X XX LO...

Page 17: ...isplay air flow rate DAMPER POS 50 Damper Position This indicates the current position of the damper in percent Range is 0 100 100 full open or maximum air DAMPER TARGET 50 Target damper target in VVT...

Page 18: ...tpoint Setup of Setpoint limits day minimum maximum F C selection See page 18 INPUT Input Shows supply air temperature reading Shows if VAV and BACnet modules are attached See page 19 OUTPUT Output Al...

Page 19: ...damper full close PRESS MENU TO EXIT Exit This will exit the info menu if you select Yes Note Info menu will automatically time out after 60 seconds Balancing Menu Scroll through with Up and Down butt...

Page 20: ...Unocc Dpr Pos When Advantage is unoccupied damper will rest at this position Range 0 100 Default 0 INLET SIZE 10 INCHES Inlet Size Size of the diffuser inlet factory set K FACTOR 1500 K Factor If no D...

Page 21: ...is heating setpoint when unoccupied Range 10 0 F 100 0 F Default 62 0 F NITE COOL SET 83 0 F Night Cool Setpoint Advantage will maintain this cooling setpoint when unoccupied Range 10 0 F 100 0 F Defa...

Page 22: ...ure to enable heating Cold Switch set SAT temperature to enable cooling Neutral Mode Force Cool Locks the diffuser in the cooling mode Neutral Mode Force Heat Locks the diffuser in the heating mode RM...

Page 23: ...hts When using Motion T Stat output controls room lights USED AS FORCE OFF Force Off Output de energized at all times USED AS FORCE ON Force On Output energized at all times REHEAT TYPE ON OFF Reheat...

Page 24: ...tputs this voltage on Auxiliary Analog pin when there is a maximum call for cooling Default 10 0 VDC AUX HEAT MIN 0 0 VDC Auxiliary Heat min Voltage Outputs this voltage on Auxiliary Analog pin when t...

Page 25: ...ddress are only read on startup See Device Instance below and Addressing on page 29 30 DEVICE INST 101 Device Instance This is the software BACnet address MUST be unique on your building site Range 1...

Page 26: ...low or Skys SOUND OPTIONS LIMITS ONLY Thermostat Sound Limits Only stat will beep when user tries to exceed a limit default All off beeper disabled All on stat will beep when user exceed a limit or st...

Page 27: ...application model Square Round Swirl or Linear PRESS MENU TO EXIT CO2 Settings Menu Menu item will only appear if thermostat with CO2 sensor connected See thermostat with CO2 for more details Advanta...

Page 28: ...r is a 35 foot plenum rated network cable to simplify installation in the field Local addresses can be set at each Advantage diffuser using the on board DIP switches The media access control MAC addre...

Page 29: ...The terminating can be done with a 100 ohm resistor across the and lines Advantage Diffusers have the option for enabling termination via a DIP switch or by a software menu selection Turning on termi...

Page 30: ...twisted pairs one for and one for NET COM Twisted pair and reference or 3 conductor Low capacitance 17pF or less Plenum rated FT6 CMP ratings 100 120 ohm Balanced CAT5 CAT5E CAT6 network cable has ex...

Page 31: ...Service Menu Hold down the Menu button on the LCD Thermostat for 5 seconds until prompted for a passcode use and to enter the passcode DOWN UP UP DOWN The screen will now display Service Menu Applicat...

Page 32: ...the same speed Acutherm controllers are defaulted to a baud rate of 76800 but can be changed to 38400 19200 or 9600 For a network segment with all Acutherm controllers including Acutherm PRTU systems...

Page 33: ...is obtained NOTE Each device on a network segment must be set to run at the same speed or baud rate Description Default Value Factory Notes Mac Address 6 Value limited to 1 99 Tier 1 x100 58 Value lim...

Page 34: ...ne Signals Supply Air Temperature Test Procedure Advantage Response Response Time Varies allow at least 5 minutes COLD Supply Air Temperature 2 F 1 C cooler than Room Temperature Adjust setpoint for m...

Page 35: ...some power cables to another jack Faulty Cable or Connector First Disconnect all cables and connectors originating from problem outlet Next Reconnect first C35 cable only If Red fault LED lights cabl...

Page 36: ...ports 9600 19200 38400 76800 baud rates 2x RJ45 connections Green Transmit LED Red Receive LED MAC address settable through DIP switches or LCD thermostat Device Instance settable through LCD thermost...

Page 37: ...Advantage Digital VAV Diffusers PRODUCT OVERVIEW INSTALLATION INSTRUCTIONS 35 acutherm com ACUTHERM ADVANTAGE Manual NOTES...

Page 38: ...ve Suite 280 Dublin CA 94568 USA Tel 1 510 785 0510 Send your questions to info acutherm com This document contains the most current product information as of this printing For the most up to date pro...

Reviews: