Model PD6000 Analog Input Process Meter Instruction Manual
8
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
Main display: 0.60" (15 mm) high, red LEDs
Second display: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking
DISPLAY
INTENSITY
Eight user selectable intensity levels
DISPLAY
UPDATE RATE
5/second (200 ms)
OVERRANGE
Display flashes
999999
UNDERRANGE
Display flashes
-99999
PROGRAMMING
METHODS
Four front panel buttons, digital inputs, PC and multi-point
linearization utility, or cloning using Copy function.
NOISE FILTER
Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS
Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION
All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN
DISPLAY
Max/min readings reached by the process are stored until
reset by the user or until power to the meter is turned off.
PASSWORD
Three programmable passwords restrict modification of
programmed settings.
Pass 1: Allows use of the F1–F3 function keys
Pass 2: Allows use of the F1–F3 function keys and chang-
ing the set/reset points
Pass 3: Restricts all programming and F1–F3 keys
Note: Digital inputs are not password protected, except programming functions.
NON-VOLATILE
MEMORY
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
POWER
OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC
±
10%, 15 W max
FUSE
Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 meters may share one 5 A fuse
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals P+ & P-: 24 VDC
±
5% @ 200 mA max (standard),
(12/24 VDC powered models rated @ 100 mA max).
5 or 10 VDC @ 50 mA max, selectable with internal jumper J4.
NORMAL MODE
REJECTION
Greater than 60 dB at 50/60 Hz