Model PD6000 Analog Input Process Meter Instruction Manual
32
Setting the Input Signal (
input
)
Enter the
Input
menu to set up the meter to display current (
mA
) or
voltage (
volt
) inputs.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or
±
10 VDC signals.
Setting the Decimal Point (
dEc pt
)
The decimal point may be set with up to five decimal places or with no
decimal point at all.
Pressing the Right arrow moves the decimal point one place to the right
until no decimal point is displayed, and then it moves to the leftmost
position.
Setting the Display Parameter & Intensity (
dsplay
)
The main display (
Big
) can be programmed to display:
1. Process
value
2. Relay set points
3. Max & min values
The small display (
Little
) can be programmed to display:
1. Process
value
2. Relay set points
3. Max & min values
4. Engineering units or custom legends
5. Off (no display)
Display Intensity: The meter has eight display intensity levels to give the
best performance under various lighting conditions. Select intensity 8 for
outdoor applications.