Model PD6000 Analog Input Process Meter Instruction Manual
Low-Flow Cutoff (
CutofF
)
The low-flow cutoff feature allows the meter to be programmed so that
the often-unsteady output from a differential pressure transmitter, at low
flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will
display zero below the cutoff value. Programming the cutoff value to
zero disables the cutoff feature.
Analog Output Programming (
AoutPr
)
The
Analog Output Programming
menu is used to program the behavior
of the 4-20 mA output. The following parameters and functions are pro-
grammed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. PV)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to
scale the 4-20 mA output
Analog Output Source
The source for generating the 4-20 mA output may be assigned to the
process variable, maximum or minimum value reached by the process,
or one of the set points.
Pv
Source
Source
AoutPr
Set Points
1 - 8
max
Source
min
Source
Analog Output Calibration
To perform the analog output calibration it is recommended to use a
milliamp meter with a resolution of at least 0.1 µA to measure the output
current. The values saved internally during this procedure are used for
scaling the 4-20 mA output in the
Setup
menu.
67