Model PD6000 Analog Input Process Meter Instruction Manual
INSTALLATION
There is no need to remove the meter from its case to com-
plete the installation, wiring, and setup of the meter for most
applications. Instructions are provided for 12 VDC meter power
and for 5 or 10 V transmitter power applications, see page 16.
Unpacking
Remove the meter from box. Inspect the packaging and con-
tents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact
your supplier or the factory for assistance.
Panel Mounting Instructions
•
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm
x 45 mm). Refer to Figure 1 below, for more details.
•
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
•
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
•
Remove the two mounting brackets provided with the meter (back-off
the two screws so that there is ¼" (6.4 mm) or less through the
bracket. Slide the bracket toward the front of the case and remove).
•
Insert meter into the panel cutout.
•
Install mounting brackets and tighten the screws against the panel.
To achieve a proper seal, tighten the mounting bracket screws
evenly until meter is snug to the panel along its short side. DO NOT
OVER TIGHTEN, as the rear of the panel may be damaged.
3.622" (92mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
Refer to page
87 for mounting
dimensions
-0.000 (-0.0mm)
Figure 1. 1/8 DIN Panel Cutout Dimensions
15