Service center of POWTRAN technology company
My future ,drive and control
1. Must perform motor auto-turning first when apply
the vector control mode
CODEb
Description of Code
Range of setting
b0
.01
rated power
15.000
b0
.02
rated frequency
50Hz
b0
.03
rated rotation speed
1450
b0
.04
rated voltage
380V
b0
.05
rated current
32A
b0
.37
motor auto-turning selection
2:complete Rotational auto-tuning
1.Disconnect the load from motor .(This is important ,otherwise can‟t get the
Motor parameters precision ,the perform of vector can‟t work well )
2. put the b.01 , b0.02, b0.03, b0.04, b0.05 according nameplate of motor.
3.Put the b0.27to 2, the light of TUN will on in the keyboard ,and then press
The RUN key ,motor will start auto-turning automatic .
4. It will display „END” in the menu at the end of auto-turning .it means the auto
Turning has performed successfully .