Service center of POWTRAN technology company
My future ,drive and control
PID control for constant pressure water supply for 4~20mA
Parameters setting
F0.00
Control mode
2:V/F
2
F0.03
frequency setting source
selection
8:PID control setting
8
F0.13
acceleration time
0.1
~
3600.0s
25
F0.14
deceleration time
0.1
~
3600.0s
25
F0.11
Command sourse selection
Terminal control
1
F1.00
DI1 terminal function selection
DI1 use for FWD
1
F1.03
DI4 terminal function selection
DI4 use for fault reset
9
F1.02
DI3 terminal function selection
DI3 use for PID pause function
22
E2.01
PID value set by keyboard
0.0%
~
100.0%
60
E2.02
PID feedback source
0:analog input feedback signal AI2
1
E2.04
PID setting feedback range
0 ~65535
100
E2.05
PID inversion cutoff frequency
0
.
00 to F0.19(maximum frequency)
0.00HZ
E2.13
proportional gain (Kp)
0.00
~
100.00
100.00
E2.14
integration time (Ti)
0.00
~
100.00
0.25s
F7.46
Awakens frequency
dormancy frequency
(
F7.48
)
to maximum
frequency (F0.19)
0.00Hz
F7.47
Awakens delay time
0.0s to 6500.0s
0.0s
F7.48
Dormancy frequency
0.00Hz to awakens frequency(F7.46)
0.00Hz
F7.49
Dormancy delay time
0.0s to 6500.0s
0.0s