10.3.5. three line control mode
F0.11
command source selection
1:Terminal command channel (LED ON)
1
F1.00
DI1 function selection
1.Forward running direction
1
F1.01
DI2 function selection
2.Reverse running direction
2
F1.02
DI3 function selection
3:Three wire mode running control
3
F1.10
Terminal command mode
2. three line control mode 1
2
First of all , you need short DI3 with COM.
When you short DI1 with COM ,the inverter will run FWD.
When you short DI2 with COM ,the inverter will run REV.
When the DI3 and COM open,the inverter stop.
DI1 and DI2 is pulse signal,and DI3 is switch signal
3 wire control mode
FWD REV
Stop
Command
on
off
on
FWD
off
on
on
REV
X
X
off
stop